Danfoss logo
AKS 4100 and AKS 4100U - 280 mm

Liquid level sensor, AKS 4100 U, Coaxial version D22

084H4536

Design: Coaxial version D22, Parts included: HMI with EN,DE,FR,ES Language, Connection size [in]: 3/4, Connection type: NPT, Insertion length [mm]: 279, Supply voltage [V] DC: 14 - 30

Product specifications

Characteristic
Value
Ambient temperature range [°C] [max]80 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]176 °F
Ambient temperature range [°F] [min]-40 °F
ApprovalCELLC CDC TYSKUKCA
CE evaluatedYes
Connection size [in]3/4
Connection typeNPT
DesignCoaxial version D22
DG Indicator ProfileNot relevant for dangerous goods
Enclosure rating IPIP67
In scope of WEEE and contain batteriesNo
Insertion length [in]11.000 in
Insertion length [mm]279 mm
Load resistance max. [Ohm]500 Ohm
Material DescriptionAKS 4100U Coaxial 11 in. with HMI
Max. Working Pressure [bar]100.0 bar
Max. Working Pressure [psig]1450 psig
Output signal [mA] [max]20 mA
Output signal [mA] [min]4 mA
Packing formatSingle pack
Characteristic
Value
Parts includedHMI with EN,DE,FR,ES Language
Power consumption [W]0.7 W
Product accessoriesLiq. level switch accessories
Product descriptionLiquid Level Sensor
Product groupSensors
Product lineIndustrial Refrigeration
Product nameLiquid level sensor
Product TypeAKS 4100 U
Quantity per packing format1 pc
REACH Candidate List substancesNo
RefrigerantsR717
ServiceableLiq. level switch spare parts
Supply voltage [V] DC [max]30 V
Supply voltage [V] DC [max]30.00 V
Supply voltage [V] DC [min]14 V
Supply voltage [V] DC [min]14.00 V
Temperature range [°C] [max]100 °C
Temperature range [°C] [min]-60 °C
Temperature range [°F] [max]212 °F
Temperature range [°F] [min]-76 °F

General specifications

Characteristic
Value
Gross weight3.79 Kilogram
Net weight2.4 Kilogram
Characteristic
Value
Volume13.984 Liter
EAN5702428934039