Danfoss logo
Gas sensor DST G54B

Gas sensor, DST G54B, R454B

073G2073

Alarm threshold [LFL %]: 9, Supply voltage [V] AC: 24, Supply voltage [V] DC: 24.00, Measuring range [°C]: -40 - 80, Electrical connection: Mini Mate-N-Lok, Electrical connection size: 6 pin, Output signal: Relay, Specification key: DST G54B-B0-09-2AAB-LC001-I

Product specifications

Characteristic
Value
Alarm reset [LFL hysteresis %]2,5
Alarm reset Relay5 minutes
Alarm threshold [LFL %]9
Ambient temperature range [°C] [max]95 °C
Ambient temperature range [°C] [min]-40 °C
Ambient temperature range [°F] [max]200 °F
Ambient temperature range [°F] [min]-40 °F
CE evaluatedYes
Communication configurationCustomer Relay
DG Indicator ProfileNot relevant for dangerous goods
Electrical connectionMini Mate-N-Lok
Electrical connection size6 pin
Electrical connection standardEN 60529
Enclosure designRound Ø6 black
Enclosure rating IPIP54
Flame ratingUL 94 V-0
Housing materialPA66 25% Glass fiber
In scope of WEEE and contain batteriesNo
Material DescriptionSensor DST G54B-B0-09-2AAB-LC001-I /80
Measuring range [°C] [max]80 °C
Measuring range [°C] [min]-40 °C
Measuring range [°F] [max]175 °F
Measuring range [°F] [min]-40 °F
Modbus terminationNone
Mounting interface2 brackets 180 dgr
Characteristic
Value
Output signalRelay
Packing formatIndustrial pack
Pin 1+ supply
Pin 2- common
Pin 3Not connected
Pin 4Not connected
Pin 5Relay input
Pin 6Relay NO
Pressure range [bar] [max]1.20 bar
Pressure range [bar] [min]0.70 bar
Pressure range [psi] [max]17.40 psi
Pressure range [psi] [min]10.15 psi
Product groupSensors
Product lineSensing Solutions
Product nameGas sensor
Product TypeDST G54B
Quantity per packing format80 pc
Recovery time [min]<5
RefrigerantsR454B
Rel. Humidity conditions0 - 100
Response time [S]<15
Specification keyDST G54B-B0-09-2AAB-LC001-I
Supply current max. [mA]300 mA
Supply voltage [V] AC24 V
Supply voltage [V] DC24.00 V

General specifications

Characteristic
Value
Gross weight58 Gram
Net weight46 Gram
Characteristic
Value
EAN5715162953167