Danfoss logo
HJM/Z125 & HJM/Z144 & HJM/Z160 D39

Optyma™, OP-HGZ144D39Q

115F0321

Segment usage: Medium Back Pressure, Refrigerants: R404A; R452A; R134a; R513A; R448A; R449A, Compressor power supply [V]: 230/3/60

Product specifications

Characteristic
Value
Air flow @ 60Hz [m³/h]13980 m³/h
ApplicationsHBPMBP
Compressor modelMTZ144-3
Compressor power supply [V]230/3/60
Condenser typeQ8
Contain batteriesNo
CoolselectorFilterActive models
DG Indicator ProfileNot relevant for dangerous goods
DLLP2
DescriptionOP-HGZ144D39Q
Electrical codeQ
FamilyOptyma™
Fan current @ 60Hz [A]3.50 A
Fan diameter [mm]600 mm
Fan power consumption @ 50Hz [W]500 W
Fan power consumption @ 60Hz [W]600 W
Fan power supply [V/Ph/Hz]230/1/60
Frequency [Hz]60 Hz
Characteristic
Value
High value of nominal voltage at 60Hz [V]230 V
Low value of voltage range at 60Hz [V]200 V
Material DescriptionCONDENSING UNIT HGZ144D39Q
Model numberOP-HGZ144D39Q
No. of phases (compressor)3
No. of phases (fan)1
Number of fans2
Phase3
Product TypeOptyma™ D39
Product groupCondensing Units
Product lineCondensing Units
Product nameBare unit
Receiver volume [L]18.0 L
RefrigerantsR134aR404AR448AR449AR452AR513A
Segment usageMedium Back Pressure
Speed PlatformFixed-speed
TechnologyReciprocating
VersionD39

General specifications

Characteristic
Value
Gross weight252 Kilogram
Characteristic
Value
Net weight234 Kilogram