Danfoss logo
 OP-MSIM068/080/099/108/MLW05/W09E/G

Optyma™ Slim Pack, OP-MSIM068MLW05G

114X7312

Segment usage: Medium Back Pressure, Refrigerants: R404A; R452A; R407A; R134a; R454C; R407F; R513A; R448A; R455A; R449A, Compressor power supply [V]: 230/1/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]5200 m³/h
ApplicationsMBP
ApprovalCE
CE evaluatedYes
Capacity controlFixed speed
China RoHS complianceOut of scope
Compressor Low pressure volume (L)3.70 L
Compressor modelMLZ030T5
Compressor power supply [V]230/1/50
Condenser Coil Internal Volume [L]1.62 mm³
Condenser typeG7
Condenser volume (L)1.62
Connection typeSolder
Contain batteriesNo
CoolselectorFilterActive models
DG Indicator ProfileNot relevant for dangerous goods
DLLP5
DescriptionOP-MSIM068MLW05G
EU RoHS complianceOut of scope
Electrical codeG
FamilyOptyma™ Slim Pack
Fan blade size [mm]560.000 mm
Fan cowl/grill typeB3
Fan current @ 50Hz [A]1.60 A
Fan diameter [mm]560 mm
Fan power consumption @ 50Hz [W]140 W
Fan power output @ 50Hz [W]72 W
Fan power supply [V/Ph/Hz]230/1/50
Filter Drier Volume (L)0.35
Frequency [Hz]50 Hz
HMBP Cooling capacity [kW] (R513A)4.74 kW
HMBP Cooling capacity range [kW] (R513A)3.7 to 7 kW
High value of nominal voltage at 60Hz [V]255 V
LBP Cooling capacity range [kW] (R452A)Not available for this condition / refrigerant
Length [mm]464 mm
Liquid line connection [in]1/2 in
Characteristic
Value
Low value of voltage range at 60Hz [V]187 V
MBP Cooling capacity [kW] (R449A)7.41 kW
MBP Cooling capacity range [kW] (R449A)8.3 to 17 kW
MCC32 A
Material DescriptionOP-MSIM068MLW05G
Min fuse rating [A]40 A
Model numberOP-MSIM068MLW05G
No. of phases (compressor)1
No. of phases (fan)1
Number of fans1
Phase1
Product TypeOptyma™ Slim Pack W05 (A2L)
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)N,N-dimethylacetamide (CAS no. 127-19-5)
Receiver approvalCEEAC
Receiver typeVertical
Receiver volume [L]6.2 L
RefrigerantsR134aR404AR407AR407FR448AR449AR452AR454CR455AR513A
SCIP dossier no.517dd61a-f0c7-4249-8639-17b34a9dfce2
SCIP dossier product nameOPTYMA W05
Segment usageMedium Back Pressure
Sound power @ 50Hz [db(A)]79 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]68 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]48 dBA
Speed PlatformFixed-speed
Suction connection size [in]7/8 in
TechnologyScroll
Total height [mm]825.0 mm
VersionW05
Voltage 50Hz [V]187 V
Voltage 50Hz [V] [Max]255 V
Volume (L)0.107 L
Width [mm]1105.00 mm

General specifications

Characteristic
Value
Gross weight96 Kilogram
Net weight76 Kilogram
Volume0.423 Cubic meter
Characteristic
Value
EAN/UPC5702424592394
Proposition 65Cancer and Reproductive Harm