Danfoss logo
OP-LSQM014/018DPW09G - OP-MSGM018/021SCW09G - OP-MSBM009/012/014DYW09G - OP-MSGM012/015SCW09G -  OP-LSVM014/016DPW09G - OP-MSSM012/015/018/021SCW09G - OP-MSTM008/009DYW09G - OP-MSTM012/014DPW09G - OP-MSTM018DXW09G

Optyma™ Slim Pack, OP-MSTM018DXW09G

114X7290

Segment usage: Medium Back Pressure, Refrigerants: R404A; R452A; R454C; R448A; R455A; R449A, Compressor power supply [V]: 230/1/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]3300 m³/h
ApplicationsMBP
ApprovalCE
CE evaluatedYes
Capacity controlFixed speed
China RoHS complianceOut of scope
Compressor modelDX18Tba
Compressor power supply [V]230/1/50
Condenser Coil Internal Volume [L]0.58 L
Condenser typeA7
Condenser volume (L)0.39
Connection typeSolder
Contain batteriesNo
CoolselectorFilterActive models
DG Indicator ProfileNot relevant for dangerous goods
DLLP5
DescriptionOP-MSTM018DXW09G
EU RoHS complianceOut of scope
Electrical codeG
FamilyOptyma™ Slim Pack
Fan blade size [mm]450.000 mm
Fan cowl/grill typeB1
Fan current @ 50Hz [A]0.47 A
Fan diameter [mm]450 mm
Fan power consumption @ 50Hz [W]60 W
Fan power output @ 50Hz [W]68 W
Fan power supply [V/Ph/Hz]230/1/50
Filter Drier Volume (L)0.17
Frequency [Hz]50 Hz
HMBP Cooling capacity range [kW] (R513A)Not available for this condition / refrigerant
High value of nominal voltage at 60Hz [V]255 V
LBP Cooling capacity range [kW] (R452A)Not available for this condition / refrigerant
Length [mm]364 mm
Characteristic
Value
Liquid line connection [in]3/8 in
Low value of voltage range at 60Hz [V]187 V
MBP Cooling capacity [kW] (R449A)1.38 kW
MBP Cooling capacity range [kW] (R449A)0.8 to 1.5 kW
MCC9 A
Material DescriptionOP-MSTM018DXW09G
Min fuse rating [A]10 A
Model numberOP-MSTM018DXW09G
No. of phases (compressor)1
No. of phases (fan)1
Number of fans1
Phase1
Product TypeOptyma™ Slim Pack W09 (A2L)
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
REACH Candidate List substancesLead (CAS no. 7439-92-1)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)N,N-dimethylacetamide (CAS no. 127-19-5)
Receiver approvalCEEAC
Receiver typeVertical
Receiver volume [L]1.3 L
RefrigerantsR404AR448AR449AR452AR454CR455A
SCIP dossier no.909c64e4-e03b-4416-9d18-aed12abdd98a
SCIP dossier product nameOPTYMA W09
Segment usageMedium Back Pressure
Sound pressure level 50Hz (@10 m distance) [db(A)]39 dBA
Speed PlatformFixed-speed
Suction connection size [in]3/8 in
Total height [mm]530.0 mm
VersionW09
Voltage 50Hz [V]187 V
Voltage 50Hz [V] [Max]255 V
Volume (L)0.035 L
Width [mm]910.00 mm

General specifications

Characteristic
Value
Gross weight63 Kilogram
Net weight53 Kilogram
Volume311.131 Liter
Characteristic
Value
EAN/UPC5702424586416
Proposition 65Cancer and Reproductive Harm