Danfoss logo
OP-MPI/XM068/80/108MLP00E/G;OP-MPL/PM028/035/044VVLP01/E

Optyma™ Plus INVERTER, OP-MPPM044VVLP01E

114X4334

Segment usage: Medium Back Pressure, Refrigerants: R404A; R407A; R407F; R448A; R449A, Compressor power supply [V]: 400/3/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]5200 m³/h
ApplicationsMBP
Basic Data Text TemplateХолодопроизводительность 9033 Вт, потребляемая мощность 5190 Вт (Тисп=<br>-10С, Тос=+32С, при частоте вращения компрессора 100 об/с), хладагент<br>R404a. Напряжение питания: компрессор - 400В/3ф/50Гц, вентилятор –<br>230В/1ф/50Гц.
Capacity controlInverter
China RoHS complianceOut of scope
Compressor modelVLZ044TGA
Compressor power supply [V]400/3/50
Condenser Coil Internal Volume [L]1.62 mm³
Condenser typeG7
Connection typeSolder
Contain batteriesNo
CoolselectorFilterActive models
DG Indicator ProfileNot relevant for dangerous goods
DLLP24
DescriptionOP-MPPM044VVLP01E
EU RoHS complianceOut of scope
Electrical codeE
FamilyOptyma™ Plus INVERTER
Fan blade size [mm]500.000 mm
Fan cowl/grill typeH3
Fan current @ 50Hz [A]0.96 A
Fan diameter [mm]500 mm
Fan power consumption @ 50Hz [W]220 W
Fan power output @ 50Hz [W]130 W
Fan power supply [V/Ph/Hz]230/1/50
Fan voltage @ 50Hz (max) [V] [Min]230 V
Frequency [Hz]50 Hz
HMBP Cooling capacity range [kW] (R513A)Not available for this condition / refrigerant
High value of nominal voltage at 50Hz [V]440 V
LBP Cooling capacity range [kW] (R452A)Not available for this condition / refrigerant
Length [mm]481 mm
Liquid line connection [in]5/8 in
Low value of nominal voltage at 50Hz [V]360 V
Characteristic
Value
MBP Cooling capacity [kW] (R449A)9.25 kW
MBP Cooling capacity range [kW] (R449A)8.3 to 17 kW
MCC12.1 A
Material DescriptionOP-MPPM044VVLP01E
Min fuse rating [A]20 A
Model numberOP-MPPM044VVLP01E
No. of phases (compressor)3
No. of phases (fan)1
Number of fans1
Phase3
Product TypeOptyma™ Plus INVERTER P01
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
REACH Candidate List substancesLead (CAS no. 7439-92-1)N,N-dimethylacetamide (CAS no. 127-19-5)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)
RLA10.5 A
Receiver approvalCE
Receiver volume [L]6.2 L
RefrigerantsR404AR448AR449AR407AR407F
SCIP dossier no.9c693fb6-7e2f-4820-aa0e-bb81dfaad435
SCIP dossier product nameOPTYMA P01 G7
Segment usageMedium Back Pressure
Sound power @ 50Hz [db(A)]74 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]63 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]43 dBA
Suction connection size [in]3/4 in
TechnologyScroll
Total height [mm]965.0 mm
Variable speed approved frequency50 Hz
VersionP01
Voltage 50Hz [V]360 V
Voltage 50Hz [V] [Max]440 V
Width [mm]1406.00 mm

General specifications

Characteristic
Value
Gross weight150.5 Kilogram
Net weight124 Kilogram
Characteristic
Value
EAN/UPC5702428564496
Proposition 65Cancer and Reproductive Harm