Valves for thermostatic sensors
Product types shown: 6

KOVM
KOVM is 3-way mixing valve which can, among others, be used for the water-side regulation of terminals in the form of “fan-coils” or as induction units. It can be combined with RAVK self-acting thermostatic actuator.
Main data:- DN 15
- kvs 0.63 - 2.0 m3/h
- PN 10
- Temperature: Circulation water / glycolic water up to 30 %: 2 … 90 °C
- Connections: Int. thread
- DN 15

VG / VGF
VG and VGF are pressure relieved 2-way normally open (NO) valves, designed to be combined with:
- AVT thermostatic actuators
- STM safety temperature monitors
- STL safety temperature limiters
- For domestic hot water (DHW) production: hot water tanks; storage charge systems; instantaneous domestic hot water production.
- In mixing loops and room heating systems as well.
- AVT thermostatic actuators

VGS
VGS is pressure relieved 2-way normally open (NO) valves for steam, designed to be combined with:
- AVT Temperature actuators;
- STM Safety temperature monitors;
- STL Safety temperature limiters;
- AMV(E) 20 / AMV(E) 30 electrical actuators
- AMV(E) 23 / AMV(E) 33 electrical actuators with spring return function.
Main data:- DN 15-25
- kVS 1.0-6.3 m3/h
- PN 25
- Temperature: Steam/circ. water/glycolic water up to 30 %: 2 … 200 °C
- Connections: Ext. thread (weld-on, thread and flange tailpieces)
- Flow and return mounting
- AVT Temperature actuators;

VGU / VGUF
VGU and VGUF are pressure relieved 2-way normally closed (NC) valves, designed to be combined with:
- AVT Temperature actuators;
- AMV(E) 20 / AMV(E) 30 electrical actuators;
- AMV(E) 23 / AMV(E) 33 electrical actuators with spring return function.
Main data:- DN 15-50
- kVS 4.0 -25 m3/h
- PN 25
- Temperature: Circulation water / glycolic water up to 30%: 2 …150 °C
- Connections: Ext. thread (weld-on, thread and flange tailpieces), Flange
- Flow and return mounting
- AVT Temperature actuators;

VMT
VMT is 2-way seated valve primarily for use in heating systems.
It can be combined with:
• ABV and ABNV* Thermohydraulic actuators
• RAVI, RAVK and RAVV self-acting thermostatic actuators
* ABNV can be combined with VMT-/8 valves only.
Main data:
• DN 15 - 25
• kVS 1.5 - 8.0 m3/h
• PN 10
• Temperature: Circulation water / glycolic water up to 30%: 2 … 120 °C
• Connections: Ext. thread