Danfoss logo
OP-LPOM120LLP02E - OP-LPOM168LLP02E

Optyma™ Plus, OP-LPOM168LLP02E

114X3486

Segment usage: Low Back Pressure, Refrigerants: R404A; R452A; R448A; R449A, Compressor power supply [V]: 400/3/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]9500 m³/h
Air volume (EF002618)7500
ApplicationsLBP
Capacity ControlFixed speed
China RoHS complianceOut of scope
Compression method (EF013498)Scroll compressor
Compressor modelLLZ034T4A
Compressor power supply [V]400/3/50
Condenser Coil Internal Volume [L]1.97 L
Condenser typeJ7
Connection typeSolder
Connection voltage (EF003625)253
Contains batteriesNo
CoolselectorFilterActive models
Depth (EF000049)1950
DescriptionOP-LPOM168LLP02E
DG Indicator ProfileNot relevant for dangerous goods
Electrical codeE
EU RoHS complianceOut of scope
FamilyOptyma™ Plus
Fan blade size [mm]500.000 mm
Fan cowl/grill typeGrill
Fan current @ 50Hz [A]0.96 A
Fan diameter [mm]500 mm
Fan power consumption @ 50Hz [W]190 W
Fan power output @ 50Hz [W]220 W
Fan power supply [V/Ph/Hz]230/1/50
Fan voltage @ 50Hz (max) [V] [Max]253 V
Fan voltage @ 50Hz (max) [V] [Min]207 V
Frequency [Hz]50 Hz
Height (EF000040)966.000
High value of nominal voltage at 50Hz [V]440 V
HMBP Cooling capacity range [kW] (R513A/R134a)Not available for this condition / refrigerant
In scope of WEEENo
LBP Cooling capacity [kW] (R452A)7.14 kW
LBP Cooling capacity range [kW] (R452A)3.6 to 7.2 kW
Length [mm]650.0 mm
Liquid injectionYes
Liquid line connection [in]3/4 in
Low value of nominal voltage at 50Hz [V]360 V
LRA150 A
Material DescriptionOP-LPOM168LLP02E
MBP Cooling capacity [kW] (R449A)17.96 kW
MBP Cooling capacity range [kW] (R22)Not available for this condition / refrigerant
MBP Cooling capacity range [kW] (R449A)17 to 27 kW
Characteristic
Value
MCC28 A
Min fuse rating [A]32 A
Model numberOP-LPOM168LLP02E
No. of phases (compressor)3
No. of phases (fan)1
Number of fans2
Number of phases (EF000351)3
Number of receivers1
Phase3
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
Product TypeOptyma™ Plus P02
REACH Candidate List substancesLead (CAS no. 7439-92-1)N,N-dimethylacetamide (CAS no. 127-19-5)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)Bisphenol A (BPA, CAS no. 80-05-7)
Receiver approvalEACPEDRoHS
Receiver volume [L]10.0 L
RefrigerantsR404AR448AR449AR452A
RLA18 A
SCIP dossier no.8715baa0-315c-4422-97d8-0a8b45f1b46d
SCIP dossier product nameOPTYMA P02 G7 J7
Segment usageLow Back Pressure
Sound power @ 50Hz [db(A)]79 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]68 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]48 dBA
Suction connection size [in]1-1/8 in
Suitable for type of refrigerant R134a (EF013569)FALSE
Suitable for type of refrigerant R22 (EF013579)FALSE
Suitable for type of refrigerant R290 (EF013580)FALSE
Suitable for type of refrigerant R32 (EF013567)FALSE
Suitable for type of refrigerant R401a (EF013581)FALSE
Suitable for type of refrigerant R402a (EF013582)FALSE
Suitable for type of refrigerant R404a (EF013568)TRUE
Suitable for type of refrigerant R407c (EF013583)FALSE
Suitable for type of refrigerant R413a (EF013584)FALSE
Suitable for type of refrigerant R417a (EF013585)FALSE
Suitable for type of refrigerant R507 (EF013570)FALSE
TechnologyScroll
Total height [mm]966.0 mm
VersionP02
VersionDescriptionP02 : Optyma Plus with Liquid injection
Voltage 50Hz [V]360 V
Voltage 50Hz [V] [Max]440 V
Weight (EF000167)228.00
Width (EF000008)650.00
Width [mm]1835.00 mm

General specifications

Characteristic
Value
Gross weight228 Kilogram
Net weight166 Kilogram
Volume1726.725 Liter
Characteristic
Value
EAN/UPC5702428666305
Proposition 65Cancer and Reproductive Harm