Danfoss logo
OP-LPHM018SCP00G - OP-LPKM084LLP02E -  OP-LPKM098LLP02E

Optyma™ Plus, OP-LPKM084LLP02E

114X3305

Segment usage: Low Back Pressure, Refrigerants: R404A; R452A; R454C; R448A; R455A; R449A, Compressor power supply [V]: 400/3/50

Product specifications

Characteristic
Value
Air flow @ 50Hz [m³/h]5200 m³/h
Air volume (EF002618)5200
ApplicationsLBP
ApprovalCE
Capacity ControlFixed speed
CE markYes
China RoHS complianceOut of scope
Compression method (EF013498)Scroll compressor
Compressor High pressure volume (L)0.50
Compressor Low pressure volume (L)4.74 L
Compressor modelLLZ015T4LQ9B
Compressor power supply [V]400/3/50
Condenser Coil Internal Volume [L]1.62 L
Condenser typeG7
Connection typeSolder
Connection voltage (EF003625)380
Contains batteriesNo
CoolselectorFilterActive models
Depth (EF000049)531
DescriptionOP-LPKM084LLP02E
DG Indicator ProfileNot relevant for dangerous goods
Electrical codeE
EU RoHS complianceOut of scope
FamilyOptyma™ Plus
Fan blade size [mm]560.000 mm
Fan cowl/grill typeH3
Fan current @ 50Hz [A]1.60 A
Fan diameter [mm]560 mm
Fan power consumption @ 50Hz [W]140 W
Fan power output @ 50Hz [W]72 W
Fan power supply [V/Ph/Hz]230/1/50
Filter Drier Volume (L)0.35
Frequency [Hz]50 Hz
Height (EF000040)965
High value of nominal voltage at 50Hz [V]415 V
HMBP Cooling capacity range [kW] (R513A/R134a)Not available for this condition / refrigerant
In scope of WEEENo
LBP Cooling capacity [kW] (R452A)3.29 kW
LBP Cooling capacity range [kW] (R452A)1.6 to 3.6 kW
Length [mm]531.0 mm
Liquid injectionYes
Liquid line connection [in]1/2 in
Low value of nominal voltage at 50Hz [V]380 V
LRA88.5 A
Material DescriptionOP-LPKM084LLP02E
MBP Cooling capacity [kW] (R449A)9.23 kW
MBP Cooling capacity range [kW] (R22)Not available for this condition / refrigerant
Characteristic
Value
MBP Cooling capacity range [kW] (R449A)8.3 to 17 kW
MCC16.9 A
Min fuse rating [A]20 A
Model numberOP-LPKM084LLP02E
No. of phases (compressor)3
No. of phases (fan)1
Number of fans1
Number of phases (EF000351)3
Phase3
Product groupCondensing Units
Product lineCondensing Units
Product namePackage unit
Product TypeOptyma™ Plus P02 (A2L)
REACH Candidate List substancesLead (CAS no. 7439-92-1)N,N-dimethylacetamide (CAS no. 127-19-5)Cobalt dichloride (CAS no. 7646-79-9)BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7)Bisphenol A (BPA, CAS no. 80-05-7)
Receiver approvalCEEAC
Receiver typeVertical
Receiver volume [L]6.2 L
RefrigerantsR404AR448AR449AR452AR454CR455A
RLA10.9 A
SCIP dossier no.8715baa0-315c-4422-97d8-0a8b45f1b46d
SCIP dossier product nameOPTYMA P02 G7 J7
Segment usageLow Back Pressure
Sound power @ 50Hz [db(A)]74 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]63 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]43 dBA
Suction connection size [in]3/4 in
Suitable for type of refrigerant R134a (EF013569)FALSE
Suitable for type of refrigerant R22 (EF013579)FALSE
Suitable for type of refrigerant R290 (EF013580)FALSE
Suitable for type of refrigerant R32 (EF013567)FALSE
Suitable for type of refrigerant R401a (EF013581)FALSE
Suitable for type of refrigerant R402a (EF013582)FALSE
Suitable for type of refrigerant R404a (EF013568)TRUE
Suitable for type of refrigerant R407c (EF013583)FALSE
Suitable for type of refrigerant R413a (EF013584)FALSE
Suitable for type of refrigerant R417a (EF013585)FALSE
Suitable for type of refrigerant R507 (EF013570)FALSE
TechnologyScroll
Total height [mm]965.0 mm
VersionP02
VersionDescriptionP02 : Optyma Plus with Liquid injection
Voltage 50Hz [V]380 V
Voltage 50Hz [V] [Max]415 V
Volume (L)0.112 L
Weight (EF000167)164.00
Width (EF000008)1441
Width [mm]1441.00 mm

General specifications

Characteristic
Value
Gross weight164 Kilogram
Net weight138 Kilogram
Volume738.39 Liter
Characteristic
Value
EAN/UPC5702424595357
Proposition 65Cancer and Reproductive Harm